ADDENDA NO 002 signed000
architects
ADDENDUM NO.2
To Drawings and Specifications dated September 26, 2012
for City of Schertz - Animal Adoption Center
Prepared By: O'Neill Conrad Oppelt Architects, Inc.
Addendum Date: November 16, 2012
This addendum shall be considered part of the Contract Documents for the above - mentioned
project as though it had been issued at the same time and shall be incorporated integrally
therewith. Where provisions of the following supplementary data differ from those of the original
Contract Documents, this Addendum shall govern and take precedence.
Bidders are hereby notified that they shall make any necessary adjustment in their estimates on
account of this addendum. It will be construed that each Bidder's proposal is submitted with full
knowledge of all modifications and supplemental data specified herein.
CLARIFICATIONS:
Item
Reference
Description
C2 -1
Location of RFCSP
All responses to the RFCSP, that are received on time as
A. & B.
listed in Section 2.13 and to the location listed in Section
2.05, will be publically opened at the City Council
S2 -2
Section 00 1105, 3.06
Chambers, 1400 Schertz Parkway, Shertz, Texas, 78154,
Attachments: Selection
Building #4 at 10:30 AM, Thursday, November 29, 2012.
Criteria
DO NOT DROP OFF RESPONSES AT THE CITY COUNCIL
CHAMBERS.
C2 -2
Section 10 9400, Kennel
Kennel Doors and partial wall dividers listed in
Doors & Partitions
specifications are referring to Alt. No. 4. The Base Bid for
kennels is CMU walls and chain link gates and top.
C2 -3
Window Coverings
No window coverings are required.
C2 -4
Pest Control
There is no requirement for pest control pre- treatment.
C2 -5
Chain link fencing at
6' tall Chain link that runs in front of overhead doors should
Doors 117.3 & 134.8
be run between 4 posts, anchored to slab, and include 3'
wide gate at center that allow for overhead doors to be
open and closed.
C2 -6
Special Shoring
NO special shoring is anticipated for this project, so NO
Require ents
special shoring requirements are included.
C2 -7
Section 00 4100, 1.13,
If not a Corporation, Corporate Seal is Not required, just
B., 1.
print full name of firm.
C2 -8
Fire Alarm Mfg.
The City of Shertz has NO preferred fire alarm
manufacturer.
C2 -9
Section 13 3419, 1.06 &
Use a frame drift of H /300, not H /400 as stated in
Sheet S1.1
specifications.
SPECIFICATIONS:
Item
Reference
Description
S2 -1
Section 00 5000, 1.01,
Replace sections in their entirety with ATTACHED revised
A. & B.
AIA A101 Owner General Contractor Agreement & AIA
A201 General Conditions.
S2 -2
Section 00 1105, 3.06
Replace Selection Criteria in its entirety with ATTACHED
Attachments: Selection
"RFCSP 12 -PK 42 C 01 Evaluation Form for General
Criteria
Contractor for Animal Adoption Center"
P: \1120 COS Animal Care Facility \Construction Phase \Addenda \Add 2 \ADDENDA NO 002.docx
000
architects
S2 -3
Section 00 3100, 1.01, B.
Add ATTACHED Geotechnical Engineering Study
D2 -1
Sheet A2.1
Prepared by Raba Kistner Consultants, Inc. for Project No.
ASA12- 008 -00, Dated February 22, 2012.
S2 -4
Section 11 9400, 2.02,
Replace text IT Adoption Kennels." with "Adoption Kennels
A.
Rm. 117 and Stray Dogs Kennels Rm. 134 , Per Alternate
D2 -2
Sheet A6.3
No. 4."
S2 -5
Section 11 9400, 2.02,
Replace text "2' wide door with one -way SSK latch." with
D2 -3
B., 1.
"4' wide (full width of kennel) door with one -way latch ".
S2 -6
Section 00 4100, C. & D.
Remove paragraph C. & D. in their entirety.
S2 -7
Section 00 4100, 1.12, E.
Remove note "GC" on line items 6., 8., & 12..
S2 -8
Section 08 4313, 2.01,
Add " & Columbia Commercial Building Products:
C.
www.ccbpwin.com" as an acceptable manufacturer.
S2 -9
Section 08 3326, 2.01,
Add "9. DBCI Commercial Roll -up Doors: www.dbci.com"
A.
as an acceptable manufacturer.
S2 -10
Flat Screen TV Brackets
Provide blocking as necessary per mfg.
recommendations for 3 flat screen TV's , one each in
rooms 101, 114 & 118. TV's to be Owner provided. (3) Wall
D2 -6
Sheet Al. 1
mounted brackets to be provided by Gen. Contractor.
Brackets to based on LG LSW200BG EX slim Wall Mount for
37 ", 42 ", 46" or 47" TV's., or Equal. Bracket to include
angled HDMI and Component Adapters, +/- 15 degree
swivel and tilt.
S2 -11
Section 27 1000
Revise specification section 27 1000, 2.02, b., 5. such that
part numbers as follows: "TE connectivity part Number
1 4791 54 -2 / Leviton part number 41 AW2- 100 ".
S2 -12
Section 13 3419, 1.05,
Replace text "2009" with "2006 ". This project is designed
A.
based on the 2006 International Building Code.
S2 -13
Section 11 9400, 2.01
Add "C. Suburban Surgical Inc. Co.: www.suburban
sur ical.com" as an acceptable manufacturer.
DRAWINGS: ARCHITECTURAL
Item
Reference
Description
D2 -1
Sheet A2.1
Add Window Type 22 and Window Type 23 on ATTACHED
8.5" x 1 1 ", Sheet ADDN2.1. Replace Window Type Callouts
"W4" with "W18" as shown on ATTACHED 8.5" x 11 ", Sheet
ADDN2.2.
D2 -2
Sheet A6.3
Add Window Type 22, 23, & 24 on ATTACHED revised Sheet
A6.3. Added Glass type to Window Types 18 & 19.
D2 -3
Sheet A6.1, Door
Door No. 117.3 & Door No. 134.8, replace Width of "22' -0""
Schedule
with "12' -0 "" and Height of "20' -0 "" with "12' -0"".
D2 -4
Detail 13/A7.0
Lockers are to have 4" metal base per specifications and
not concrete. Lockers have sloped top per specifications
and not flat.
D2 -5
Sheet A1.0
Replace sheet A1.0 with ATTACHED revised Sheet A1.0.
Revised Fire lane and Added location for new Fire
Hydrant on 1 /Al .0. Added note that digital message
board is for future installation, refer to MEP for elec.
require ents on 3 /Al .0.
D2 -6
Sheet Al. 1
Replace sheet A1.1 with ATTACHED revised Sheet A1.1.
Updated structural notes on detail 2 /Al .1.
P: \1120 COS Animal Care Facility \Construction Phase \Addenda \Add 2 \ADDENDA NO 002.docx
000
architects
DRAWINGS: CIVIL
Item
Reference
Description
CD2 -1
Sheet C1.1
Replace sheet C1.1 with ATTACHED revised Sheet CM
and note the following changes:
• Added 1 " water meter for landscape irrigation
• Differentiated between proposed 5' interior and
exterior sidewalks due to the fact that the existing
sidewalk onsite has a decorative brick lug running
along one side. This raised the need for two separate
sidewalk details
• Updated existing sidewalk callouts to reflect the
decorative brick lug
• Added detail to proposed sidewalk tie -in callouts
noting transition length, etc.
• Adjusted location of proposed fire hydrant assembly &
valve
• Added proposed electrical drop location
• Added additional conduits & altered conduit from
Visitors Center
• Added concrete stoop to eastern side of building
• Changed concrete "ramps" coming out of the
adoption & stray dog kennel areas to be concrete
stoops & updated callouts
• Change ramp coming out of sally port to be a 8'x3'
concrete stoop & updated callout
• Added bearings & distances for property line boundary
to the north (adjacent to Dietz Creek)
• Removed previous flagpole locations & added a single
flagpole to concrete pad in front of building
• Changed conduit callouts to reference MEP sheets
CD2 -2
Sheet C1.2
Replace sheet C1.2 with ATTACHED revised Sheet C1.2
and note the following changes:
• Same as C1.1
• Added water line dimensioning for Alternate #3
CD2 -3
Sheet C4
Replace sheet C4 with ATTACHED revised Sheet C4 and
note the following changes:
• Same as C1.1 (where relevant)
• Altered length of handicap accessible ramp &
sidewalk ramp coming up to the building due to
grading changes
• Added an inset detailing dimensions of the eastern
asphalt driveway for Base Bid.
• Added water line dimensioning for Alternate #3
• Added additional dimensional control coordinate
points to point table
P: \1120 COS Animal Care Facility \Construction Phase \Addenda \Add 2 \ADDENDA NO 002.docx
000
architects
CD2 -4
Sheet C5.1
Replace sheet C5.1 with ATTACHED revised Sheet C5.1
SD2 -1
Sheet S1.1, OF -6
and note the following changes:
• Same as C1.1 (where relevant)
• Altered grading for handicap and sidewalk ramps in
front of the building
• Changed grading of ramps (previously shown) into
kennels and sally port to reflect change to stoops
• Added additional spot elevations
CD2 -5
Sheet C5.2
Replace sheet C5.2 with ATTACHED revised Sheet C5.2
and note the following changes:
• Same as C1.1 (where relevant)
• Added a section detailing concrete swales into pond
CD2 -6
Sheet C5.4
Replace sheet C5.4 with ATTACHED revised Sheet C5.4
and note the following changes:
• Same as C1.1 (where relevant)
• Added reinforcement to concrete curb detail
• Added additional sidewalk details due to there being
two different types of sidewalk onsite (see comments
for C1.1 above)
• Added pavement junction detail
• Altered pavement width for "Proposed Concrete
Pavement Section" detail from 25' to 24'
CD2 -7
Sheet C6.1
Replace sheet C6.1 with ATTACHED revised Sheet C6.1
and note the following changes:
• Same as C1.1 (where relevant)
• Adjusted water line callouts to account for changes to
alignment
• Added an 8" cap to end of fire hydrant assembly if
Alternate #3 is not constructed
• Added angular dimensioning to sanitary sewer line
• Added detailed dimensioning of water line for
Alternate #3
• Removed a portion of note 2 Of OSHA Trench Safety
Notes, specifically the portion referring to the cost of
trench protection being incidental to the cost of the
pipe
CD2 -8
Sheet C6.3
Replace sheet C6.3 with ATTACHED revised Sheet C6.3
and note the following changes:
• Removed OSHA Trench Safety Notes since they appear
on sheet C6.1
DRAWINGS: STRUCTURAL
Item
Reference
Description
SD2 -1
Sheet S1.1, OF -6
Add " +/- 2" in front of "%' in Site Preparation Soil Supported
Foundations Note OF -6 and Remove " +/- 2" in front of "6
inches or less. ".
P: \1120 COS Animal Care Facility \Construction Phase \Addenda \Add 2 \ADDENDA NO 002.docx
000
architects
DRAWINGS: MEP
Item
Reference
Description
MEPD2 -1
Sheet P2.0, Plumbing
Replace Plumbing Keyed Notes #13 in its entirety with " 6"
Keyed Notes #13
FIRE SPRINKLER MAIN ENTRY. REFER TO CIVIL FOR SERVICE
CONNECTION. REFER TO P2.1 FOR CONTINUATION WITHIN
THE BUILDING."
MEPD2 -2
Sheet MEP2.1
Revise Electrical Keyed Note #4 as follows: "PROVIDED (1)
4" CONDUIT UNDERGROUND FROM IT ROOM AT ANIMAL
ADOPTION CENTER TO VISITOR CENTER. CONDUIT SHALL
ENTER VISITOR CENTER ADJACENT TO FIBER ENTRANCE.
TERMINATION SHALL BE UP THRU FLOOR TO POINT 4"
ABOVE FINISH FLOOR. CONTRACTOR SHALL VERIFY EXACT
LOCATION OF FIBER ENTRY. SEE 4/T2.1 FORIT ROOM
DETAILS."
MEPD2 -3
Sheet E2.1
Remove wall mounted device adjacent to ISO 124.
MEPD2 -4
Sheet E3.1
Revise keyed note #3 to say: "MOUNT NOTED
RECEPTACLES AND DATA OUTLETS AT (1) EACH AT 18" AND
72 " ". Revise power and data layout for Training Room
#114, per ATTACHED SK -1. Revise location of FACP panel
from Manager 131 into Administration 101b, per
ATTACHED SK -2.
END OF ADDENDUM NO. 2