Fire Dept. Commercial & Res. Dev. Guidelines Schertz 3.10.2015Schertz Fire Department  Fire Marshal’s Office  Commercial & Residential Site Development Guidelines These guidelines are provided to assist the developer of commercial and residential properties to meet the requirements of the City of Schertz's Fire Marshal’s Office.  The information provided are guidelines only and are not intended to address  all requirements.  Currently the City references the 2012 IFC, 2012 IBC, & most current NFPA edition. COMMERCIAL DEVELOPEMENTS  Fire Lane Coverage  •An approved surface (lane) must be in installed prior to going vertical with any construction* •All exterior walls shall be within 150' of an approved fire lane • • Required Radii •14’ height clearance over fire lanes •All fire lanes shall be paved either asphalt or concrete, unless alternate material is approved . • Cul‐de‐sac length is 500’ Maximum (measured from the center of road to center of cul-de-sac)• Minimum unobstructed width access lanes of 24' Two points of fire department access or approved turnaround is required after 150' Fire Hydrants  • • • •Fire Hydrant branch lines shall connect to an 8" Main •Not located in the fire lane radii •Fire Department Connections shall be located not more than 120' or less than 30' from the nearest FH •An approved water supply shall be on site prior to installation or construction of combustable materials • •City of Schertz requires all hydrants to come with (5 1/4") Storz quick connection by Approved Manufacturers 1400 Schertz Parkway Schertz, Texas 78154 210‐619‐1300   6/23/2015  Site Development Guidelines  Page 1 of 2  •Must have a hydrant locator reflector (type II blue bump) installed perpendicular to roadway Building Sprinkled – 600’ spacing Building without sprinkler– 400’ spacing Fire Hydrants located every 300' in a commercial/industrial area fire Hydrants located every 500' in residential areas 1 hydrant allowed on 6" Main Fire Lane Width 24’ – 25' Inside Radii, 50’ Outside Radii  Private Fire Hydrants (All Red), Public Fire Hydrants (Red & White), see Detail •Distance to nearest hydrant: Schertz Fire Department  Fire Marshal’s Office  Commercial Site Development Guidelines  Fire Sprinklers Required  •Buildings 10,000 sq. ft. or greater and Residential above 5,000 sq. ft. •Changing in Certificate of Occupantcy will require to update facilities to current NFPA code #101 •Highest floor level 30’ or more requires a stand pipe •Underground Fire Mains shall be a minimum of 8” •FDC location shall be shown and labeled on all site plans. Knox FDC caps and boxes are required Underground Storage Tanks  •Off‐street/fire lane loading space •Distance to property lines, building easements-follow NFPA guidlines • Out of Fire Lane• Separate Permit required through the Fire Marshal’s Office Above Ground Storage Tanks  •Tanks must be in accordance with most current edition of pertinant NFPA. •Distance to property lines, buildings, public ways • •Out of fire lane Off‐street/fire lane loading space Gates and Fences  • Gates through fences must be located to maintain 150’ fire lane coverage and be a minimum of 5’ wide 1400 Schertz Parkway Schertz, Texas 78154 210-619-1300   6/23/2015 Site Development Guidelines  Page 2 of 2  A-2 occupancy-5,000 ft2/100 occupancy load• Electric gates shall require approved Knox switch and approved locks Must include means of emergency means to open in case of power loss • •